Inner View of Regulator :
Brief Specifications :
Jindal's rectifiers are designed for continuous rated with adequate margin of safety and are capable of working of 100% load factor.
The standard specifications are as follows :
Input Voltage
|
380-440 Volts, 3-Phase, 50 Hz, AC supply.
|
Output Voltage
|
Fixed rated maximum DC voltage or variable from zero to maximum rated voltage.
|
Output current
|
From zero to rated maximum DC current
|
Temperature Rise
|
Less than 35 degrees Celsius above ambient at the top of the oil.
|
Efficiency
|
- 12 V Rectifier : 82%.
- 100 V Rectifier : 94%.
- More than 250 V Rectifier : > 97%.
- 24 V Rectifier : 90%.
- 200 V Rectifier : 96%.
|
Ripple Content
|
<5% Optional feature of 1% Ripple Content also available.
|
Insulation
|
A class for oil cooled.
|
The standard equipment consists of :
- Linear type continuously variable Rolling Contact type ON - LOAD Voltage Regulator (with straight +- connection) operable electrically with the help of raise / lower push buttons and a step-synch motor or manually with the help of a 'T' handle.
- Copper wound delta / double star (hexa - phase) step down transformer as per IS 2026.
- Copper wound Inter phase transformer.
- Junction Box fox three phase input terminals and Bus Bars for DC Output.
- Meter panel with DC Voltmeter and DC Ammeter and raise / lower push buttons.
- Thermometer Pocket.
- Oil fill plate.
- Oil level gauge.
- Oil drain out valve.
- Lifting lugs.
- Wheels for uni - directional movement.
- Name plate with complete specs of the equipment.
- Earthing terminals.
- Indicator lamps for RYB input AC supply, as per IS : 1248.
- First Filling of Oil.
Starting Circuitry :
Jindal's Rectifiers are designed for 3 phase, 50 Hz, AC input supply and are available for operations at any voltage between 380 and 440 volts, covering a wide range of voltage fluctuations. It is recommended that the input of the rectifier should be connected through a proper protective device, to provide positive protection to personnel and the system, in the event of maintenance or in case a fault occurs.
DC Output Control :
The function of the variable output controls is to control the voltage or current or its operating range by varying input voltage to the main transformer primary. The DC output voltage variable is achieved steplessly 0-100% by means of an ON LOAD roller type Jindal's make voltage regulator.
|